™®June 1999 (2) 10318817WARNINGTo avoid death, personal injury or propertydamage, do not use this furnace if any partof the furnace has been under wat
10The filters should be inspected and cleaned or changedevery two months or as required. In some installations, thefilters can be inspected and cleane
11V. For More InformationMost questions can be answered by the local Amana dealer. Check with dealer first if needing any further informationregarding
12VI. Safety LabelsNOTE: If safety labels are missing or illegible, contact the installing dealer or Amana Customer Service Department forordering inf
2As a professional installer you have an obligation toknow the product better than the customer. Thisincludes all safety precautions and related item
3WARNINGTo avoid personal injury or fire, minimumclearances to combustible surfaces mustbe followed.7. Make certain the required clearances for the fu
4MINIMUM UNIT CLEARANCES TO COMBUSTIBLESURFACES (HORIZONTAL INSTALLATIONS - GDCONLY)A SIX INCH TOP CLEARANCE IS ALSO REQUIRED.12"0"6"
5The vent system must slope toward the furnace for drain-age of condensate. Provision must be made to drain thecondensate and protect the condensate d
6Cool/HeatSwitchFan SwitchCool/HeatTemperatureControl DialRoom TemperatureThermostatThermostat ControlLeverSystemSwitchFanSwitchActionOFF AUTO NoneCOO
7Flame Roll-OutProtectionDeviceFigure 8Roll-Out Protection Device - CounterflowPosition (GDC)Flame Roll-OutProtectionDeviceFigure 9Roll-Out Protection
8RESET AFTER CONTROL LOCK-OUTIf ignition has not been achieved for any reason after threeignition cycles, the electronic control module will lock-outt
9sibility to keep air filters clean. NOTE: Dirty filters are themost common cause of inadequate heating or coolingperformance.UPFLOW FILTERS (GUC, GUX