WARNING
PERSONAL INJURY HAZARD
To prevent death, personal injury or
property damage due to fire or explo-
sion caused by a propane gas leak, in-
stall a gas detecting warning device.
Since rust can reduce the level of odor-
ant in propane gas, a gas detecting warn-
ing device is the only reliable way to
detect a propane gas leak. Contact a
local propane gas supplier about install-
ing a gas detecting warning device.
IN CANADA THE CONVERSION SHALL BE CAR-
RIED OUT IN ACCORDANCE WITH THE REQUIRE-
MENTS OF THE PROVINCIAL AUTHORITIES HAV-
ING JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN/CGS B149.1 AND
B149.2 INSTALLATION CODE.
WARNING
PERSONAL INJURY HAZARD
To prevent death, serious personal in-
jury or property damage due to fire or
explosion caused by a propane gas leak,
install a gas detecting warning device.
If the propane gas furnace is installed in
a basement, an excavated area or a con-
fined space, a warning device is required
due to:
Propane gas is heavier than air and
any leaking gas can settle in any low
areas or confined spaces.
Propane gas odorant may fade, mak-
ing the gas undetectable except with
a warning device.
If the presence of gas is suspected, fol-
low these instructions:
Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your build-
ing.
Immediately call your gas supplier
from a neighbors phone. Follow the
gas suppliers instructions.
If you cannot reach your gas sup-
plier, call the fire department.
This kit includes: installation instructions, propane ori-
fices, valve conversion kits with instructions, conver-
sion rating plate, conversion date certificate, wire ties,
and screen/turbulator removal warning tag.
Installation
CAUTION
PERSONAL INJURY HAZARD
The gas supply must be shut off prior to
disconnecting the electrical power, be-
fore proceeding with the conversion.
1. Remove the gas manifold by removing the burner
box front cover (not required on all models), cutting
the wire ties, disconnecting the gas valve low volt-
age wires, and removing the four manifold mount-
ing screws. See Figure 1.
Figure 1
Gas Manifold Removal
2. Replace natural gas orifices with the altitude appro-
priate propane orifices (Figure 2B) specified in Table
1. Tighten orifices with a box-end wrench. Do not
use a socket wrench, as it could damage the ori-
fices. Do not over-tighten. Do not cross thread.
Propane Gas Orifices
Standard Altitude Data High Altitude Data
Model
Kit
Number
Orifice
Altitude
(ft)
Pilot
Orifice
Kit
Number
Orifice
Altitude
(ft)
GUIA, GUIB
GCIA, GCIB
LPTK07A #55 0 - 7500 N/A HALP06 #56 7500 - 11000
GUIC
GCIC
LPTK07A #55 0 - 6000 N/A HALP06 #56 6000 - 11000
GUC, GUD
GUX, GDC
GCD, GCC
LPTK07A #55 0 - 4500 N/A HALP08 #56 4500 - 9500
PGB**C
PGD**C
LPTK07A #55 0 - 6000 BBR12 HALP06 #56 6000 - 9500
GUIS, GCIS
LPTK07A #55 0 - 2000* N/A N/A N/A N/A
* See the Amana Distributor for High Altitude Kits for installations above 2000 feet.
Table 1