WRAP-UP
1. Replace the cover on the control box.
2. To complete the outdoor unit installation, refer to the outdoor unit
Installation Manual.
3. When the system installation is complete and the outdoor temperature
is 50°F or higher, run the system to confirm proper operation:
If any sparking, unusual noises, or unusual odors are noticed,
immediately disconnect the electrical power, then recheck wiring and
components.
Upon the initial call for cooling, the compressor and outdoor fan
should start. The high and low pressure switches should both be
closed.
End the call for cooling, and then immediately begin another call for
cooling. Assuming that no indoor fan time delay relay is present, the
indoor fan should restart immediately, but the compressor and
outdoor fan should not restart for about 3 minutes.
To avoid possible equipment damage, do not adjust airflow or
refrigerant charge in an attempt to cause the pressure switches to
open. The high pressure switch opens at about 400 psi, and closes
at about 300 psi. The PCK01A low pressure switch opens at about
35 PSI, and closes at about 85 PSI. A properly operating cooling
system will not experience pressure extremes enough to cause
these pressure switches to open.
4. While the system is operating, perform a final refrigerant leak check on
the tees and pressure switches. If a leak is found, tighten the joint
slightly and retest. Repeat until all leaks are eliminated.