4
®
is a trademark of Maytag
Worldwide N.V. and is used under license to
Goodman Company, L.P. All rights reserved.
CAUTION
Avoid servicing the low ambient control while the unit is operating. The rotating fan blades
could cause serious injury.
If measurement of the high side pressure is required, use the liquid line valve on the outside of the unit. Also note
that most electrical measurements for the compressor can be performed adequately near the contactor, rather than
at the compressor itself. If you must service the area near the compressor or low ambient control with the unit in
operation, consider doing the following:
a. Disconnect the electrical power
b. Unplug the outdoor fan motor.
c. Carefully reconnect the electrical power.
d. Operate the compressor only long enough to complete the needed service function. Note that the lack of outdoor
airflow will cause the head pressure to be substantially higher than normal. Suction pressure and amp draw will
be higher than normal. Subcooling will be less than normal.
SERVICER’S NOTE