Amana PGD**C Manual de Instruções Página 5

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 12
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 4
5
Package Gas-Electric Cont’d
PILOT ORIFICE REPLACEMENT
PACKAGE GAS-ELECTRIC UNITS EQUIPPED WITH PI-
LOT
The pilot orifice must be replaced on Packaged Gas-Electric
Units equipped with a Honeywell “Smartvalve” and pilot
ignition system.
1. Disconnect pilot assembly wiring from gas valve and
remove natural gas pilot orifice from the pilot assem-
bly.
Orifice Conversion
2. Replace with propane gas pilot orifice provided and
reconnect wiring. Use care, do not damage igniter.
Pilot Orifice
Figure 1
Package Unit Pilot Orifice
Table 1
Type Model
Kit
Number
Altitude
(ft)
Burner
Orifice
Pilot
Orifice
Kit
Number
Altitude
(ft)
Burner
Orifice
Pilot
Orifice
GUIA,GUIB,
GCIA, GCIB
LPTK09 0 - 7500 #55 N/A HALP09 7501 - 11000 #56 N/A
GUIC, GCIC,
GUID
LPTK09 0 - 6000 #55 N/A HALP09 6001 - 11000 #56 N/A
GUIS, GCIS,
GUIV
LPTK09 0 - 7000 #55 N/A HALP09 7001 - 8500 #56 N/A
GUC, GUD,
GUX, GDC,
GCD, GCC
LPTK09 0 - 4500 #55 N/A HALP09 4501 - 9500 #56 N/A
GUCA, GCCA LPTK09 0 - 7000 #55 N/A HALP10 7001 - 11000 #56 N/A
GUVA LPTK09 0 - 7000 #55 N/A HALP11 7001 - 11000 #56 N/A
PGA**C***D
PGB**C***D
PGD**C***D
LPTK09 0 - 6000 #55 BBR12 HALP09 6001 - 9500 #56 BBR12
PGA**C***E
PGB**C***E
PGD**C***E
LPTK09 0 - 6000 #55 N/A HALP09 6001 - 9500 #56 N/A
Propane Gas Orifices
Non-Condensing
Gas Furnaces
Condensing Gas Furnaces
Package Gas-Electric Units
Product Standard Altitude High Altitude
Vista de página 4
1 2 3 4 5 6 7 8 9 10 11 12

Comentários a estes Manuais

Sem comentários